Operation Manual FireSpy® Tracker T1000, T2000, T8000 Fire Alarm Systems DOCUMENT REV CN 780-0923 C 1208
Contents 1 2 HSI #780-0923 FireSpy Tracker Operation Manual 6 2.5 System conditions and annunciation 2.5.1 Normal standby condition Display The s
3 B A 5 4 2 HSI #780-0923 FireSpy Tracker Operation Manual 7 2.5.3 Non-normal condition (browsing event list) Display After pressing A / B or C /
Contents 1 2 HSI #780-0923 FireSpy Tracker Operation Manual 8 2.5.8 Programming mode While the panel is in programming mode, the panel is still pe
3 B A 5 4 2 HSI #780-0923 FireSpy Tracker Operation Manual 9 Smoke detector control Smoke detectors need to control both on and off states of fans
Contents 1 2 HSI #780-0923 FireSpy Tracker Operation Manual 10 This page left intentionally blank for duplex printing.
B 4 5 A 3 HSI #780-0923 FireSpy Tracker Operation Manual 11 3 Test and maintenance When any test or maintenance procedure is conducted, all buildin
Contents 1 2 3 HSI #780-0923 FireSpy Tracker Operation Manual 12 Perform maintenance of any other system devices in accordance with the manufacture
B 5 A 4 HSI #780-0923 FireSpy Tracker Operation Manual 13 4 Using the menu system 4.1 Accessing the menu system To access the menu system, press
Contents 1 2 3 4 HSI #780-0923 FireSpy Tracker Operation Manual 14 4.6 Text and number entry Entering text Several places in the menu system ask f
B A 5 HSI #780-0923 FireSpy Tracker Operation Manual 15 5 Maintenance menu 5.1 Level 1 main menu The date format is yyyy.mm.dd. The time format is
This page left intentionally blank for duplex printing.
Contents 1 2 3 4 5 HSI #780-0923 FireSpy Tracker Operation Manual 16 5.5 Menu 2.2: Silent Walk Test While on this screen, devices that go into ala
B A 5 HSI #780-0923 FireSpy Tracker Operation Manual 17 Appendix A. Glossary Terms used in this manual are defined as follows: Acknowledge- An ope
Contents 1 2 3 4 5 A HSI #780-0923 FireSpy Tracker Operation Manual 18 General Alarm- Simultaneous operation of all the notification appliances on
B A HSI #780-0923 FireSpy Tracker Operation Manual 19 Style Z- A Class A NAC configuration in which a circuit reports troubles from grounds, shorts
Contents 1 2 3 4 5 A HSI #780-0923 FireSpy Tracker Operation Manual 20 This page left intentionally blank for duplex printing.
HSI #780-0923 FireSpy Tracker Operation Manual Appendix B. Operating instructions Frame these instructions and place adjacent to the panel for rea
HSI #780-0923 FireSpy Tracker Operation Manual Harrington Signal Inc. 2519 4th Ave., P.O. Box 590, Moline, IL 61265 (800) 577-5758 ⋅⋅⋅⋅ (30
B 3 4 5 A 1 2 Contents HSI #780-0923 FireSpy Tracker Operation Manual i Contents 1 Preliminary Information ...
Contents HSI #780-0923 FireSpy Tracker Operation Manual 4.3 About the numbering used ...
B 3 4 5 A 2 1 HSI #780-0923 FireSpy Tracker Operation Manual 1 1 Preliminary Information 1.1 Safety messages – Please read before proceeding Peopl
Contents 1 HSI #780-0923 FireSpy Tracker Operation Manual 2 The programming technician is ultimately responsible for conformance to the applicable
3 B A 5 4 2 HSI #780-0923 FireSpy Tracker Operation Manual 3 2 Operation This manual describes the operation of FireSpy Tracker 1000, 2000, and 800
Contents 1 2 HSI #780-0923 FireSpy Tracker Operation Manual 4 2.3.8 Releasing: Fast Release Modules or detectors assigned to operate as a Fast Rel
3 B A 5 4 2 HSI #780-0923 FireSpy Tracker Operation Manual 5 reset will return the panel to its normal operating condition. To perform the fast res