OPTIONS:
AUX+24VDCOUTPUT
Donot
CONNECTIONOF AN AUX AUDIOSOURCE
OPTIONAL SUPERVISORY CIRCUIT
- TB2-4,8,9&10
Theseterminalsprovideamax.200mA ofregulated24VDCpowerforauxiliaryfunctions. exceed200mA loadcombinedon
theseterminals.ForconnectiontoListedGeneralSignaldevicesonly(Non-FireProtectiveSignalingapplications). Terminal4activation
isprogrammedintheU6ePROMchip.Standardchipsareprogrammedfor TB2-4togoactive+24VDCunderthefollowingconditions:
AuxSignal Active, Aux AudioEnable,BellCircuit Active,RSI Active.Reprogrammingofthesefunctionsmustbedoneatthefactory
andrequirereplacingepromU6.
- TB2-1&2
AnauxaudiosourcefromadditionalpagingequipmentmaybeconnectedtotheEVAX25/50/100toaugmentanexistingpagingsystem.
Itisnotintendedforcontinuoussignalinput,butmaybeusedforpagingapplications.Forsuchanoperationthe Aux AudioEnableinput,
TB2-6,mustbepoweredfromIntV+, TB2-9. Thisistoinsurethatintheeventofanalarm,theauxaudiowillnotoverridetheevacuation
signal.SeeWiringDiagram5forconnectiondetail.
- TB3-1&2
Inplaceofnormalsupervisionviathesignalingcircuit,analternatemethodmaybeemployedusinganysupervisorycircuitfromtheFACP.
Connectionwouldbemadeto TerminalBlock3, Ter.1and2. ThiswouldprovideanormallyclosedconnectiontotheEOLRon Ter.3
and4. TherelaycontactinthecircuitwillopenuponanytroubleconditionandreportanopencircuittroubletotheFACP.
jumpershortingblocks A andBmustberemovedfrom ifacircuitistobeconnectedinthismanner.SeeOptionalSupervisory
Circuit Application(WiringDiagram2)forconnectiondetail.
InnormalstandbytheGreenLEDwillremainon.
InalarmconditiontheRedLEDwillremainonaslongastheunitisinalarm.GreenLEDwillalsoremainon.
AlarmSequenceFactorysettings:
Alarm Tone- AlarmSignal5seconds/DigitalMessageplays/ AlarmSignal5seconds/DigitalMessageplays/ AlarmSignal
5seconds/DigitalMessageplays/unitrevertsto AlarmSignaluntilalarmconditioniscleared.IftheMiciskeyeditwilloverride
boththetoneandthemessagesoadirectbroadcastmaybemade.Ifthisoccursduringtheinitialsequencethedigitalmessage
willberesetandwillnotplay.
WhentheMiciskeyedorwhenthemessageisplayedtheGreenLEDwilldim. TheintensityoftheGreenLEDwillvarywith
thelevelofthebroadcastaudio. Thisistruein Alarmconditionaswell.
Underafaultcondition,the YellowLEDwillremainon. TheGreenLEDwillflash. Thenumberofflashesdisplayacodedepending
onthespecifictypeoffault.WhenthereisafaultconditionthecontactconnectingtheFACP signalcircuittotheEOLRwillopen
indicatingthefaulttothepanelwhichwillprovideannunciation.Duringagroundfaultcondition, YellowLED4willilluminate.
InputVoltage120VACat60Hz120VACat60Hz120VACat60Hz
InputCurrent1.4 A@120VAC0.8 A@120VAC1.2 A@120VAC
InputCurrent(Battery)0.18 A Standby0.13 A Standby0.60 A Standby
1.0 A Alarm1.0 A Alarm2.60 A Alarm
0.31 A Standbyw/AuxLoad0.26 A Standbyw/AuxLoad1.20 A standbyw Auxload
Outputpower25Watt50Watt100Watt
Freq.Response800-2800Hz400-4000Hz400-4000Hz
OutputVoltage25/70VRMSSelectable25/70VRMSSelectable25/70VRMSSelectable
*Optional24VDCinput0.6 A Standby0.6 A Standby0.18 A standby
1.0 A Alarm1.0 A Alarm2.50 A Alarm
2.9 A Sine3.4 A Sine6.4A Sine
OutputProtectionPowerLimited,OpenandShortCircuitprotected
NOTE, J1
SPECIFICATIONS:
EVAX25EVAX50EVAX100
OPERATION
*InputcurrentmeasurementsaredeterminedbytestconditionsunderUL 1711.Sinerepresentsmeasurementsmade
whileunitproducesacontinuousnon-distortedsinewaveof1Khzintotheratedloadof25/50/100Watratedoutput
voltage. Alarmistheaveragecurrenttheunitexperiencesdeliveringanalarmsignal, TemporalWhoop,totherated
load.Standbyisthecurrentdrawoftheunitwithallnormalpoweronandaux.terminalsfullyloaded.Battery
Standbyiscurrentdrawfromthebatteriesonlossofpowerandotherwisenormalstandby.
100wattMODELS
TheEVX-100isacompleteVoiceEvacuation .Itis equippedwithapowertransformeroracabinet.
TheEVAX100isacompleteVoiceEvacuation .Itisequippedwithapowertransformerandacabinet.
TheEVX-100Eisacompleteslaveamplifierwithbuilt-intonegenerator.Itiscapableofoperatingasaslaveamplifierwhenconnectedto
theEVX-100,whichsuppliessourceaudiototheslave.Itisalsocapableofoperatingasastand-aloneVoiceEvacuationSystemwithonly
toneandmicrophoneamplification.
Module not
Panel
DifferentModelnumbersarederivedfromtheamplifiersizesusedtogether: Thesemultipleamplifierconfigurationsare
Factorysetupandpre-wired. Thefollowingareintheirowncabinetwithpowertransformers. TheyarecompletePanels.
EVAX100Contains:1)EVX-1001)SpeakerCircuit
EVAX150Contains:1)EVX-100and1)EVX-50E2)SpeakerCircuits
EVAX200Contains:1)EVX-100and1)EVX-100E2)SpeakerCircuits
EVAX100EContains:1)EVX-100E1)SpeakerCircuit
EVAX150EContains:1)EVX-100Eand1)EVX-50E2)SpeakerCircuits
HARRINGTON
FIREALARM
SIGNALINC.
ISO9001Certified
25194th AvenueMoline,IL 61265
(309)762-0731FAX(309)762-8215
www.harringtonsignal.com
P/N1-5001REV.G
Page3of8